Re: 4 ft Toilet -to- stack max in Seattle?
Posted by Terry Love on February 23, 2004 at 16:39:21:
In response to Re: 4 ft Toilet -to- stack max in Seattle?

: My friendly neighborhood contractor tells me that I have to run a new vent if I move my toilet more than 4ft away from the main stack/vent in my remodel. Everything I read says 6ft max for this 3" line. Anybody out there familiar with a more restrictive code in WA?

It's 6 feet for a 3"
and 6 feet for a 4"
five for 2"
42" for 1.5"