| Posted by hj on January 31, 2004 at 09:00:53: | |
|---|---|
| In response to Re: Constant Circulation? | |
|
: Hello All! If there are no zone valves then you would not be controlling the heat to the building. If there are zone valves the pump would be in a "dead end" situation most of the time which would cause premature failure. Why did the subject come up? : I have a newer Burnham boiler on a hot water heating system with radiators. Would there be any benefit to wiring up the circulator to run 24/7? Also, are there after market outdoor reset controllers available? : Thank you!
|
|