Re: RE: Water hammer/air chambers
Posted by Terry Love on March 22, 2002 at 18:34:18:
In response to Re: RE: Water hammer/air chambers

: Hey do I need to rig this stuff on all my fixtures, I did for sink but now working on shower supply, and then tub?

Casman,
They recommend them on fast closing valves.
Dishwasher, clothes washer, icemaker.

If I have a deck tub, I use them there too.
Current code requires shock arrestors, not air chambers. If an air chamber is used, there must be a means of draining it. That being the case, the shock arrestor becomes the way to go. Terry