Re: Sewage ejection system
Posted by Terry Love on May 02, 19100 at 19:43:12:
In response to Re: Sewage ejection system
: I installed a sewage injection system in our basement 1 year ago. I went down stairs and it looks as if the liquid is rising over the pump. Is it clogged up? I have no instuctions on the pump and don't want it to ruin my carpet.

Lori,
The float switch needs to float up before the pump comes on. Is it to the overflow level of the basin, or raising in the basin? Automatic operation has 9" - 14" "On" level and, 2" - 6" "Off" level range with adjustable remote float switch.
The first thing to check, would be the power to the unit. Has the breaker tripped?

The link below has some pump information to one brand of sewage pump, which may be helpful for yours. Terry