Re: Underfloor Heating Probs
Posted by Dave H on March 01, 1999 at 17:53:33:
In response to Re: Underfloor Heating Probs
How did you make this connection?
Is it tapped off of the hot water baseboard loop or from existing radiant floors?

Typically if adding a zone of radiant heat, it needs to have a separate circ with a mixing valve so as the floor does not get too hot.





Replies to this post
There are none.