Yes there is a minimum 1/4" per foot for 3" 1/8" for 4". No maximum, but some inspectors do not like excessive fall without offsets. : Is there a min.& max. slope rate for the new pipe I must ran to connect to the city sewer, or as long as it is going down hill its fine?
|
|