Re: plumbing code question
Posted by John Scates on January 04, 19101 at 13:50:56:
In response to Re: plumbing code question
According to the Uniform Plumbing Code, Paragraph 408.6, the front must have at least 24 inches from the nearest edge to the nearest wall or door. The minimum distance to a sidewall from the center of the toilet is 15 inches.

However, for handicap accessible facilities, the front clearance must be at least 48 inches with a side distance of 18 inches (ANSI A117.1-1992)

John Scates